Skip to content
PLC - Micro800 Plug-in Modulesby Allen Bradley

2080-RTD2

Micro800 2 Channel RTD Plug-In

Micro800 System, 2-ch RTD Input (non-isolated)

Specifications

Features
2-ch RTD Input (non-isolated)
I/O Isolation
None
Accuracy
±1.0 °C @ 25 °C (77 °F)
Analogue inputs configurable
0
Analogue outputs configurable
0
Common mode rejection ratio
100 dB @ 50/60Hz
Conducted RF immunity
IEC 61000-4-6, 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
EFT/B immunity
IEC 61000-4-4: ±2kV @ 5kHz on shielded ports
Emissions
CISPR 11 (IEC 61000-6-4): Class A
ESD immunity
IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges
Input, current
0
Input impedance
>5 MΩ
Input, resistance thermometer
0
Input, resistor
1
Input signal, configurable
0
Input, thermocouple
0
Input, voltage
0
Mounting torque
0.2 nm
Nonoperating temperature
-40...85 °C (-40...185 °F), IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
Normal mode rejection ratio
70 dB @ 50/60 Hz
North American temperature code
T4
Number of analogue inputs
2
Open circuit detection time
8 to 1212
Operating temperature
-20...65 °C (-4...149 °F): IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, operating dry heat), IEC 60068-2-14 (Test Nb, operating thermal shock)
Output, current
0
Output signal configurable
0
Output, voltage
0
Power consumption
40mA @ 3.3V
Radiated RF immunity
IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz,
Resolution of the analogue inputs
14 bit
Resolution of the analogue outputs
14 bit
RTD types supported
100 Ω Platinum 385, 200 Ω Platinum 385, 500 Ω Platinum 385, 1000 Ω Platinum 385, 100 Ω Platinum 392, 200 Ω Platinum 392, 500 Ω Platinum 392, 1000 Ω Platinum 392, 10 Ω Copper 427, 120 Ω Nickel 672, 604 Ω Nickel-Iron 518
Shock
IEC 60068-2-27 (Test Ea, unpackaged shock): DIN rail mount: 25 g, nonoperating, Panel Mount: 35 g nonoperating
SIL according to IEC 61508
None
Suitable for safety functions
0
Surge transient immunity
IEC 61000-4-5: ±2 kV line-earth(CM) on shielded ports
Surrounding air temperature, max
65 °C
Terminal screw torque
0.22...0.25 Nm (1.95...2.21 in-lb) (using a 2.5 mm (0.10 in.) flat-blade screwdriver)
Type of electric connection
Screw connection
Vibration
IEC 60068-2-6 (Test Fc, operating), 2 G @ 10...500 Hz
Wire size
Solid: 0.14 mm2 AWG)...1.5 mm2 AWG) @ Rated @ 90 °C (194 °F) insulation maximum, Stranded: 0.14 mm2 AWG)...1.0 mm2 AWG) @ Rated @ 90 °C (194 °F) insulation maximum
Bulletin
2080
Series
A
Lifecycle Status
Active

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly