PLC - CompactLogix 5370 Controllersby Allen Bradley
1768-L45S
Compact GuardLogix CPU L45S 3M/1M
Compact GuardLogix CPU L45S 3M/1M
Discontinued by the manufacturer — contact us for availability, spares or a recommended replacement.
Specifications
- Class
- Progmable Logic Controller
- Embedded Network Port
- None
- L4x platform - controllers
- CompactLogix L45 Safety
- Local Programming Port
- 1 RS232
- Memory
- 3 MB
- Non Volatile Memory Option
- CompactFlash
- Safety Memory
- 1 MB
- 1768 current draw
- 5.6A @ 5V DC
- 1769 current draw
- 2.0A @ 5V DC
- Available user memory
- 3 MB standard, 1 MB safety
- Backplane current draw
- 2.1A @ 24V DC
- Communication bus
- RS-232
- Communication medium copper
- 1
- Communication medium fibre optic
- 0
- Communication medium wireless
- 0
- Communication ports
- RS-232, Fully isolated, 38.4 Kbps max
- Communications protocol
- Other
- Conducted RF immunity
- 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
- Depth
- 122.1 mm
- DIN-rail mounting
- 1
- EFT/B immunity
- ±4kV @ 5kHz on communication ports
- Emissions
- CISPR 11 (IEC 61000-6-4)
- Enclosure type rating
- None (open-style)
- ESD immunity
- 6 kV contact discharges, 8 kV air discharges
- Expandable
- 1
- Failsafe model
- 0
- Height
- 131.6 mm
- Isolation voltage
- 30V (continuous), functional insulation type, Type tested at 500V AC @ 60s, RS-232 to system
- LED indicator inputs
- 0
- LED indicator outputs
- 0
- Module expansion capacity
- Two 1768 modules, Sixteen 1769 modules
- Module location
- DIN rail or panel mount
- Number of 1768 communication modules, max
- 2
- Number of 1768 modules, max
- 4
- Number of 1768 motion modules, max
- 4
- Number of 1769 I/O modules, max
- 30
- Number of I/O banks, max
- 3
- Operating temperature
- 0 °C
- Panel-mounting screw torque
- 1.16 Nm (10 in-lb) - use M4 or #8 screws
- Power consumption
- 50.4 W
- Power dissipation
- 9.5 W
- Power supply
- 1768-PA3, 1768-PB3
- Power supply distance rating
- 4 modules
- Programming languages
- Standard task: all languages, Safety task: relay ladder, safety application instructions
- Protection for local controls
- 0
- Radiated RF immunity
- 10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
- Relative humidity
- 5...95% noncondensing
- Serial cable
- 1756-CP3 or 1747-CP3, right angle connector to controller, straight to serial port, 3 m
- Shock
- Operating: 30 G
- Slot width
- 1.5
- Standard applications available
- 1
- Storage temperature
- -40 °C
- Suitable for front mounting
- 1
- Surge transient immunity
- ±2 kV line-earth (CM) on communication ports
- Surrounding air temperature, max
- 60 °C
- Total 1768 and 1769 current draw
- 7.6A @ 5V DC
- Vibration
- 5 G @ 10...500 Hz
- Voltage type
- DC
- Weight, approx
- 0.45 kg
- Width
- 89.6 mm
- Wire category
- 2 - on communication ports
- With base plate
- 0
- With display
- 0
- With PC connection
- 1
- Bulletin
- 1768
- Series
- B
- Lifecycle Status
- Discontinued
Request a Quote
Need pricing, availability or more details? We'll get back to you.
Datasheet