Specifications
- Power
- 32 Point 24 VDC Sink Output Module
- Consist Of
- Connectors
- Depth
- 87
- digital output modules
- 32 Point 24V DC Sink Output
- Height
- 90
- I/O Isolation
- Isolated
- I/O Status Indication
- LED
- Output
- 32 Point, 24V DC Sink
- Temperature Rating
- -20…60 °C (-4…140 °F)
- Altitude
- 2000 m
- Bus current draw, max
- 175mA @ 5V DC
- Conducted RF immunity
- IEC61000-4-6: 10V, 0.15…80 MHz
- Continuous current per common, max
- 2.0A @ 60°C (140 °F)
- Continuous current per module, max
- 4.0A @ 60°C (140 °F)
- Continuous current per point, max
- 0.5A @ 60°C (140 °F
- Digital inputs configurable
- 0
- Digital outputs configurable
- 0
- EFT/B immunity
- IEC61000-4-4: 2kV @ 5kHz on signal ports
- ESD immunity
- EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect
- Hazardous environment class
- Hazardous Location, Class I, Division 2 Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213, ANSI/ISA-12.12.01)
- Heat dissipation, max
- 2.7 W @ 26.4V DC
- Isolated groups
- Group 1: Outputs 0...15, Group 2: Outputs 16...31 (internally, connected to common)
- Number of digital outputs
- 32
- Off-state leakage current, max
- 0.1mA @ 26.4V DC
- On-state current, min
- 1 mA
- On-state voltage drop, max
- 0.5A @ 0.3V DC
- Operating humidity
- 5...95% noncondensing
- Operating temperature
- -20 to 65 °C
- Operating voltage
- 10.2...26.4V DC
- Output group to backplane isolation
- Verified by one of the following dielectric tests: 1200V AC @ 2s or 1697V DC @ 2s, 75V DC working voltage (IEC Class 2 reinforced insulation)
- Output group to output group isolation
- Verified by one of the following dielectric tests: 1200V AC @ 2s or 1697V DC @ 2s, 75V DC working voltage (IEC Class 2 reinforced insulation)
- Power supply distance rating
- 6 (The module may not be more than 6 modules away from the power supply.)
- Radiated and conducted emissions
- EN50081-2: Class A
- Radiated RF immunity
- IEC61000-4-3: 10V/m, 80...2700 MHz, 80% Alitude modulation
- Redundancy
- 0
- Shock
- Operating: 30G panel mounted, 3 pulses per axis Relay ops: 7G
- Short-circuit protection, outputs available
- 0
- Signal delay, resistive load, max
- ON delay: 0.5 ms OFF delay: 4.0 ms
- Storage temperature
- -40 °C
- Suitable for safety functions
- 0
- Surge current, max
- 2.0 A (Repeatability is once every 2 s at 60 °C (140 °F) for 10 ms)
- Surge transient immunity
- IEC61000-4-5: 2 kV common mode, 1 kV differential mode
- Type of digital output
- Relay
- Type of electric connection
- Screw connection
- Type of output voltage
- DC
- Vibration
- Operating: 10...500 Hz, 5G, 0.030 in. max. peak-to-peak, 2 hr per axis Relay ops: 1.5G
- Voltage category
- 24V DC sink
- Weight
- 200 g