Skip to content
PLC - MicroLogix 1200 Controllersby Allen Bradley

1762-OB16

MicroLogix 16 Point D/O Module

MicroLogix 1200 System, 16 Point 24 VDC Source Output Module

Specifications

Power
16 Point 24 VDC Source Output Module
Class
Progmable Logic Controller
Depth
87
digital output modules
16 Point 24V DC Source Output
Height
90
I/O Isolation
Isolated
I/O Status Indication
LED
Module Interfaces
digital
Number Of Channels
16 point
Output
16 Point, 24V DC Source
Temperature Rating
0…55 °C (32…131 °F)
Altitude
2000 m
Bus current draw, max
175mA @ 5V DC (0.88 W)
Conducted RF immunity
IEC 1000-4-6: 10V @ 0.15...80MHz
Continuous current per common, max
8A @ 30°C (86 °F)
Continuous current per module, max
8A @ 30°C (86 °F)
Continuous current per point, max
1A @ 30°C (86 °F)
Digital inputs configurable
0
Digital outputs configurable
0
EFT/B immunity
IEC1000-4-4: 2kV @ 5kHz
ESD immunity
IEC1000-4-2: 4kV contact, 8kV air, 4kV indirect
Hazardous environment class
Hazardous Location, Class I, Division 2 Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)
Heat dissipation, max
2.9 W @ 30 °C (86 °F)
Isolated groups
Group 1: Outputs 0...15
Number of digital outputs
16
Off-state leakage current, max
1 mA
On-state current, min
1 mA
On-state voltage drop, max
1.0V DC
Operating humidity
5...95% noncondensing
Operating temperature
-20 to 65 °C
Operating voltage
20.4...26.4V DC
Output group to backplane isolation
Verified by one of the following dielectric tests: 1200V AC @ 1s or 1697V DC @ 1s 75V DC working voltage (IEC Class 2 reinforced insulation)
Power supply distance rating
6 (The module may not be more than 6 modules away from the power supply.)
Radiated and conducted emissions
EN50081-2: Class A
Radiated RF immunity
IEC1000-4-3: 10 V/m, 80...1,000 MHz, 80% Alitude modulation, +900 MHz keyed carrier
Redundancy
0
Shock
Operating: 30G panel mounted, 3 pulses per axis Relay ops: 7G
Short-circuit protection, outputs available
0
Signal delay, resistive load
On delay: 0.1 ms Off delay: 1.0 ms
Storage temperature, min
-40 °C
Suitable for safety functions
0
Surge current, max
2.0 A (Repeatability is once every 2 s at 55 °C (131 °F), once every s at 30 °C (86 °F) for a duration of 10 ms.)
Surge transient immunity
IEC1000-4-5: 2 kV common mode, 1 kV differential mode
Type of digital output
Relay
Type of electric connection
Screw connection
Type of output voltage
DC
Vibration
Operating: 10…500 Hz, 5G, 0.030 in. max. peak-to-peak, 2 hr per axis Relay ops: 1.5G
Voltage category
24V DC
Weight
235 g
Width
40.4 mm
Bulletin
1762
Series
A
Lifecycle Status
Active Mature

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly

Datasheet

Datasheet not available yet — request it from our team.