Skip to content
PLC - MicroLogix 1200 Controllersby Allen Bradley

1762-IT4

MicroLogix 4 Point Input Module

MicroLogix 1200 System, 4 Channel, Thermocouple/Mv Module

Specifications

Features
4 Channel, Thermocouple/Mv Module
Class
Progmable Logic Controller
Depth
87
Height
90
I/O Isolation
Isolated
I/O Status Indication
LED
Number Of Channels
4 point
Temperature Rating
0…55 °C (32…131 °F)
Thermocouple Type
4 Channel, Thermocouple/Mv Module
Accuracy
Thermocouple T: (-270...230 °C), without autocalibration ±0.3500 °C/°C with temperature drift, maximum @ 0...60 °C ambient
A/D converter type
Delta-Sigma
Analogue inputs configurable
1
Analogue outputs configurable
0
Bus current draw
50mA @ 24V DC, maximum
Cable impedance, max
25
Calibration
The module performs autocalibration upon power-up and whenever a channel is enabled. You can also prog the module to calibrate every five minutes
Channel diagnostics
Over or under range or open circuit condition by bit reporting for analog inputs
CJC accuracy
±1.3 °C
Common mode rejection
>110 dB at 60 Hz (with 10 or 60 Hz filter)
Common mode voltage range
±10V
Conducted immunity
IEC 1000-4-6: 10V @ 0.15...80MHz
ESD immunity
IEC1000-4-2: 4kV contact, 8kV air, 4kV indirect
Fast transient burst
IEC1000-4-4 2kV @ 5kHz
Hazardous environment class
Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)
Heat dissipation
1.5 total W (the W per point, plus the minimum W, with all points enabled)
Input and output group to system isolation
30V AC/30V DC working voltage type test: 500V AC or 707V DC @ 1min
Input channel configuration
Via configuration software screen or the user prog (by writing a unique bit pattern into the module’s configuration file)
Input, current
0
Input group to bus isolation
30V AC/30V DC working voltage type test: 720V DC @ 1min
Input impedance
>10 MΩ
Input, resistance thermometer
0
Input, resistor
0
Input signal, configurable
1
Input, thermocouple
1
Input, voltage
0
Module OK LED
ON: module has power, has passed internal diagnostics, and is communicating over the bus, OFF: Any of the above is not true.
Module power LED
ON: indicates power is applied
Normal mode rejection ratio
85 dB min @ 60 Hz with the 10 or 60 Hz filter selected
Number of analogue outputs
4
Open-circuit detection time
7 ms
Operating altitude
2000 m
Operating humidity
5...95% noncondensing
Operating temperature
-20 °C
Output, current
0
Output signal configurable
0
Output, voltage
0
Overload at input terminals
Maximum @ ±35V DC continuous
Radiated and conducted emissions
EN50081-2: Class A
Radiated immunity
IEC 61000-4-3: 10 V/m, 80...1000 MHz, 80% Alitude modulation, +900 MHz keyed carrier
Rated working voltage
30V DC
Recommended cable
Belden™ 8761 (shielded), shielded thermocouple extension wire for the specific type of thermocouple you are using. Follow thermocouple manufacturer’s recommendations
Repeatability
Thermocouple T: ±1.5 °C for 10 Hz filter
Resolution
15 bit plus sign
Response speed per channel
Input filter and configuration dependent
Shipping weight
220 g
Shock
Relay ops: 7.5 G panel mounted (5 G DIN rail mounted)
Storage temperature
-40 °C
Suitable for safety functions
0
Surge immunity
IEC1000-4-5: 1kV galvanic gun
Type of electric connection
Screw connection
Vibration
Relay ops: 2 G
Width
40 mm
Bulletin
1762
Series
A
Lifecycle Status
Active Mature

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly

Datasheet

Datasheet not available yet — request it from our team.