PLC - MicroLogix 1200 Controllersby Allen Bradley
1762-IR4
MicroLogix 4 Point Module
MicroLogix 1200 System, MicroLogix 4 Point Module
Specifications
- Features
- MicroLogix 4 Point Module
- Class
- Progmable Logic Controller
- Depth
- 87
- Height
- 90
- I/O Isolation
- Isolated
- I/O Status Indication
- LED
- Module Interfaces
- resistance thermom
- Number Of Channels
- 4 point
- Temperature Rating
- 0…55 °C (32…131 °F)
- Thermocouple Type
- 4 Channel, RTD/Resistance Module
- Accuracy drift
- At 0...55 °C ±0.026 °C/°C (0.026 °F/°F) for Pt 385, ±0.007 Ω/°C (0.012 Ω/°F) for 150 Ω range, ±0.023 °C/°C (0.023 °F/°F) for Pt 3916, ±0.023 Ω/°C (0.041 Ω/°F) for 500 Ω range, ±0.012 °C/°C (0.012 °F/°F) for Ni, ±0.043 Ω/°C (0.077 Ω/°F) for 1,000 Ω range,
- A/D converter type
- Delta-Sigma
- Analogue inputs configurable
- 0
- Analogue outputs configurable
- 0
- Bus current draw
- 50mA @ 24V DC, maximum
- Cable impedance
- Maximum @ 25 Ω (operating with >25 Ω will reduce accuracy)
- Calibration
- The module performs autocalibration on channel enable and on a configuration change between channels. You can also prog the module to calibrate every five minutes
- Channel diagnostics
- Over or under range or open circuit condition by bit reporting for analog inputs
- Channel to channel isolation
- ±10V DC
- Common mode rejection
- >110 dB at 60 Hz (with 10 or 60 Hz filter)
- Conducted immunity
- IEC 1000-4-6: 10 V/m, 80...1000 MHz, 80% Alitude modulation, +900 MHz keyed carrier
- ESD immunity
- IEC1000-4-2: 4kV contact, 8kV air, 4kV indirect
- Excitation current source
- 0.5 mA and 1.0 mA selectable per channel
- Fast transient burst
- IEC1000-4-4: 2kV @ 5kHz
- Hazardous environment class
- Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)
- Heat dissipation
- 1.5 total W (the W per point, plus the minimum W, with all points enabled)
- Input and output group to system isolation
- 30V AC/30V DC working voltage type test: 500V AC or 707V DC @ 1min
- Input channel configuration
- Via configuration software screen or the user prog (by writing a unique bit pattern into the module’s configuration file)
- Input, current
- 0
- Input impedance
- >10 MΩ
- Input, resistance thermometer
- 0
- Input, resistor
- 1
- Input signal, configurable
- 1
- Input, thermocouple
- 0
- Input type
- 604 Ω Nickel-Iron 518
- Input, voltage
- 0
- Module power LED
- ON: indicates power is applied
- Non-linearity
- ±0.05% (in % full scale)
- Normal mode rejection ratio
- 70 dB minimum @ 60 Hz with the 10 or 60 Hz filter selected
- Number of analogue inputs
- 4
- Open-circuit detection time
- 6 ms
- Operating altitude
- 2000 m
- Operating humidity
- 5...95% noncondensing
- Operating temperature
- -20 °C
- Output, current
- 0
- Output signal configurable
- 0
- Output, voltage
- 0
- Overload at input terminals
- Maximum @ ±35V DC continuous
- Power supply distance rating
- 6 (the module may not be more than 6 modules away from the system power supply)
- Radiated and conducted emissions
- EN50081-2: Class A
- Radiated immunity
- IEC 61000-4-3: 10 V/m, 80...1000 MHz, 80% Alitude modulation, +900 MHz keyed carrier
- Recommended cable
- Belden 8761 (shielded)
- Repeatability
- ±0.2 Ω for other resistances
- Resolution
- Input filter and configuration dependent
- Shipping weight, approx
- 260 g
- Shock
- Operating: 30 G
- Storage temperature
- -40 °C
- Suitable for safety functions
- 0
- Surge immunity
- IEC1000-4-5: 1kV galvanic gun
- Type of electric connection
- Screw connection
- Typical accuracy
- At 25 ° C (77 °F) ambient with module operating temperature at 25 °C (77 °F)
- Typical overall accuracy
- ±0.5 °C (°F) for Pt 385
- Update time
- Input filter and configuration dependent (typical)
- Vibration
- Operating: 10...500 Hz, 5 G, 0.030 in @ maximum peak-to-peak
- Width
- 40 mm
- Bulletin
- 1762
- Series
- A
- Lifecycle Status
- Active Mature
Request a Quote
Need pricing, availability or more details? We'll get back to you.
Datasheet
Datasheet not available yet — request it from our team.