Skip to content
PLC - MicroLogix 1200 Controllersby Allen Bradley

1762-IQ32T

MicroLogix 32 Point Digital Input Module

MicroLogix 1200 System, 32 Point 24 VDC Sink/Source Input Module

Specifications

Power
32 Point 24 VDC Sink/Source Input Module
Class
Progmable Logic Controller
Consist Of
Connectors
Depth
87
digital input modules
32 Point 24V DC Sink/Source
Height
90
I/O Isolation
Isolated
I/O Status Indication
LED
Module Interfaces
digital input
Number Of Channels
32 point
Special Features
sink - source
Temperature Rating
-20…60 °C (-4…140 °F)
Altitude
2000 m
Bus current draw, max
170mA @ 5V DC
Conducted RF immunity
IEC61000-4-6: 10V @ 0.15...80MHz
Digital inputs configurable
0
Digital outputs configurable
0
EFT/B immunity
IEC61000-4-4: 2kV @ 5kHz on signal ports
ESD immunity
EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect
Hazardous environment class
Hazardous Location, Class I, Division 2 Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213, ANSI/ISA-12.12.01)
Heat dissipation, max
6.8 W @ 30.0V
IEC input compatibility
Type 1
Input group to backplane isolation
Verified by one of the following dielectric tests: 1200V AC @ 2s or 1697V DC @ 2s 75V DC working voltage (IEC Class 2 reinforced insulation)
Isolated groups
Group 1: Inputs 0...7, Group 2 : Inputs 8...15, Group 3 : Inputs 16...23, Group 4 : Inputs 24...31
Nominal Impedance
4.7 kΩ
Number of commons
4
Number of digital inputs
32
Off-state current, max
1 mA
Off-state voltage, max
5V DC
ON-state current, max
6.5mA @ 30.0V DC
On-state current, min
2mA @ 15V DC
On-state voltage, min
10V DC
Operating humidity
5...95% noncondensing
Operating temperature
-20 to 65 °C
Operating voltage
10…30V DC (24 points) @ 30 °C (86 °F) 10…26.4V DC (23 points) @ 60 °C (140 °F)
Power supply distance rating
6 (the module may not be more than 6 modules away from the system power supply)
Radiated and conducted emissions
EN50081-2: Class A
Radiated RF immunity
IEC61000-4-3: 10V/m, 80…2700 MHz, 80% Alitude modulation
Redundancy
0
Shock
Operating: 30G panel mounted, 3 pulses per axis, Relay ops: 7G
Short-circuit protection, outputs available
0
Signal delay
On delay: 8.0 ms
Storage temperature, min
-40 °C
Suitable for safety functions
0
Surge transient immunity
IEC61000-4-5: 2 kV common mode, 1 kV differential mode
Time delay at signal exchange
8 ms
Type of electric connection
Screw connection
Type of voltage (input voltage)
DC
Vibration
Operating: 10 to 500 Hz, 5G, 0.030 in. max. peak-to-peak, 2 hr per axis Relay ops : 1.5G
Voltage category
24V DC sink/source
Weight
200 g
Width
40.4 mm
Bulletin
1762
Series
A
Lifecycle Status
Active Mature

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly

Datasheet

Datasheet not available yet — request it from our team.