Skip to content
PLC - MicroLogix 1200 Controllersby Allen Bradley

1762-IF4

MicroLogix 4 Point Analog Input Module

MicroLogix 1200 System, 4 Channel Current/Voltage Analog Input Module

Specifications

Features
4 Channel Current/Voltage Analog Input Module
analog input modules
4 Channel Current/Voltage Analog Input Module
Class
Progmable Logic Controller
Current Range
4-20
Depth
87
Height
90
I/O Isolation
Isolated
I/O Status Indication
LED
Module Interfaces
analog input
Number Of Channels
4 point
Temperature Rating
-20…65 °C (-4…149 °F)
A/D converter type
Successive approximation
Analog normal operating range
Voltage: -10...10V DC
Analogue inputs configurable
1
Analogue outputs configurable
0
Bus current draw, max
40mA @ 5V DC, 50mA @ 24V DC
Channel diagnostics
Over or under range or open circuit condition by bit reporting for analog inputs
Common mode rejection
>55 dB at 50 and 60 Hz
Common mode voltage range
-27 to 27V
Conducted immunity
10V @ 0.15...80MHz
Current input protection
-32 mA
ESD immunity
EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect
Fast transient burst
IEC1000-4-4: 2kV @ 5kHz
Full scale analog ranges
Voltage: -10.5...10.5V DC, Current: -21...21 mA
Hazardous environment class
Hazardous Location, Class I, Division 2 Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)
Input and output group to system isolation
30V AC/30V DC rated working voltage (N.E.C. Class 2 required) (IEC Class 2 reinforced insulation) type test: 500V AC or 707V DC @ 1min
Input, current
1
Input impedance
Voltage Terminal: 200 KΩ
Input, resistance thermometer
0
Input, resistor
0
Input signal, configurable
1
Input, thermocouple
0
Input update time
Typical: 130, 250, 290, 450, 530 ms (selectable)
Input, voltage
1
Module power LED
On: indicates power is applied
Non-linearity
±0.12% (in % full scale)
Number of inputs
4 differential (bipolar)
Operating altitude
2000 m
Operating humidity
5...95% noncondensing
Operating temperature
-20 °C
Output, current
0
Output signal configurable
0
Output, voltage
0
Radiated and conducted emissions
EN50081-2: Class A
Radiated immunity
IEC1000-4-3: 10 V/m, 80...1,000 MHz, 80% Alitude modulation, +900 MHz keyed carrier
Recommended cable
Belden 8761 (shielded), (For 1762-IT4, shielded thermocouple extension wire for the specific type of thermocouple you are using. Follow thermocouple manufacturer’s recommendations.)
Repeatability
-0.12 to 0.12%
Resolution of the analogue inputs
15 bit
Shock
Operating: 30 g
Storage temperature
-40 °C
Surge immunity
IEC1000-4-5: 1kV galvanic gun
Type of electric connection
Screw connection
Typical overall accuracy
±0.32% full scale @ -20...65 °C, ±0.24% full scale @ 25 °C
Vibration
Operating: 5 g @ 10...500 Hz, 0.030 in. max. peak-to-peak
Voltage input protection
-30 V
Weight
Shipping: 240 g (0.53 lbs.) approximately (with cartoon)
Width
40 mm
Bulletin
1762
Series
B
Lifecycle Status
Active Mature

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly

Datasheet

Datasheet not available yet — request it from our team.