PLC - ControlLogix 5580 Controllersby Allen Bradley
1756-PBXTR
Extended Temp DC Redundant Supply
ControlLogix Extended Temperature 19-32 VDC Redundant Power Supply
Specifications
- Connection Cables
- None required
- Annunciator power
- 240V AC 50/60 Hz, 240V DC @ 50mA, resistive only, 90V DC for ATEX/IECEx
- Conductor screw torque
- 0.565 nm
- Current capacity
- 4A @ 3.3V DC
- Depth
- 137 mm
- Enclosure type rating
- None (open-style)
- Height
- 175 mm
- Input power, max
- 81 W
- Input voltage at DC
- 18 V
- Input voltage, nom
- 24V DC
- Inrush current, max
- 30 A
- ISAGX
- 0
- Operating temperature
- -25 to 70 °C
- Output voltage at DC
- 5.1 V
- Pilot duty rating
- Annunciator - not rated
- Power output
- 52 W
- Power output, max
- 52 W
- Redundancy capable
- 0
- Relative humidity
- 5...95% noncondensing
- Rockwell tire and rubber rated
- 0
- Shock
- Operating: 30 G
- Suitable for safety functions
- 0
- Type of output voltage
- DC
- Type of voltage (input voltage)
- DC
- Vibration
- 2 G @ 10...500 Hz
- Voltage variation
- IEC 61000-4-29: 10 ms interruption on DC supply ports, 60% dips for 100 ms on DC supply ports, 100% dips for 50 ms on DC supply ports, ±20% fluctuations for 15 min on DC supply ports, 5 s interruptions on DC supply ports
- Weight
- 1.45 kg
- Width
- 145 mm
- Wire category
- 1 - on power ports, 3 - on annunciator ports, 3 - on 1756-CPR2 connections
- Wire size
- Power: 2.5 mm² (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max, Annunciator: 0.25…2.5 mm² (22 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulat
- Bulletin
- 1756
- Series
- A
- Lifecycle Status
- Active
Request a Quote
Need pricing, availability or more details? We'll get back to you.
Datasheet
Datasheet not available yet — request it from our team.