Skip to content
PLC - ControlLogix 5580 Controllersby Allen Bradley

1756-PB75RK

ControlLogix DC Redundant Power Supply

Conformally coated 1756 redundant power supply 19.2 - 32V DC Power Supply (5V @ 13 Amp) Input Voltage:24V DC Power 75.00 W 13.00 A on 5V 2.80 A on 24V

Specifications

Connection Cables
1756-CPR2
Output Voltage and Current
5V DC @ 13A, 3.3V DC @ 4A, 1.2V DC @ 1.5A, 24V DC @ 2.8A
Redundant Configuration
1
Annunciator power
90V DC for ATEX/IECEx
Conductor screw torque
0.565 nm
Current capacity
4A @ 3.3V DC
Depth
137 mm
Enclosure type rating
None (open-style)
Height
175 mm
Hold-up time
20 ms
Input power, max
110 W
Input voltage at DC
18 V
Input voltage, nom
24V DC
Inrush current, max
30 A
ISAGX
0
Operating temperature
0 to 60 °C
Output voltage at DC
5.1 V
Pilot duty rating
Annunciator - not rated
Power output
75 W
Power output, max
75 W @ 0...60 °C (32...140 °F)
Redundancy capable
0
Relative humidity
5...95% noncondensing
Rockwell tire and rubber rated
0
Shock
Operating: 30 G
Suitable for safety functions
0
Type of output voltage
DC
Type of voltage (input voltage)
DC
Vibration
2 G @ 10...500 Hz
Voltage variation
IEC 61000-4-29: 10 ms interruption on DC supply ports, 60% dips for 100 ms on DC supply ports, 100% dips for 50 ms on DC supply ports, ±20% fluctuations for 15 min on DC supply ports, 5 s interruptions on DC supply ports
Weight
1.45 kg
Width
145 mm
Wire category
3 - on annunciator ports, 1 - on power ports, 3 - on 1756-CPR2 connections
Wire size
Power: 2.5 mm² (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max, Annunciator: 0.25…2.5 mm² (22 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulat
Bulletin
1756
Series
A
Lifecycle Status
Active

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly

Datasheet

Datasheet not available yet — request it from our team.