Skip to content
PLC - ControlLogix 5580 Controllersby Allen Bradley

1756-PAXTR

Extended Temp AC Redundant Supply

ControlLogix Extended Temperature 85-265VAC Redundant Power Supply

Specifications

Connection Cables
1756-CPR2XT
Frequency Rating
47...63Hz
Height
6.88 in
Output Voltage and Current
5V DC @ 8A, 3.3V DC @ 4A, 1.2V DC
Annunciator power
240V AC 50/60 Hz, 240V DC @ 50mA, resistive only
Conductor screw torque
0.565 nm
Current capacity
8A @ 5.1V DC
Depth
137 mm
Enclosure type rating
None (open-style)
Input frequency
47 Hz
Input power, max
75VA/65 W
Input voltage at AC 50 Hz
85 V
Input voltage at AC 60 Hz
85 V
Input voltage, nom
120/240V AC
Inrush current, max
20 A
ISAGX
0
Operating temperature
-25 to 70 °C
Output voltage at DC
5.1 V
Pilot duty rating
Annunciator - not rated
Power output
42 W
Power output, max
42 W @ 0...60 °C (32...140 °F)
Redundancy capable
0
Relative humidity
5...95% noncondensing
Rockwell tire and rubber rated
0
Shock
Operating: 30 G
Suitable for safety functions
0
Type of output voltage
DC
Type of voltage (input voltage)
AC
Vibration
2 G @ 10...500 Hz
Voltage variation
IEC 61000-4-11: 30% dips for 1 period at 0° and 180° on AC supply ports, 60% dips for 5 and 50 periods on AC supply ports, ±10% fluctuations for 15 min on AC supply ports, >95% interruptions for 250 periods on AC supply ports
Weight
1.45 kg
Width
145 mm
Wire category
1 - on power ports, 3 - on annunciator ports, 3 - on 1756-CPR2 connections
Wire size
Power: 2.5 mm² (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max, Annunciator: 0.25…2.5 mm² (22 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulat
Bulletin
1756
Series
A
Lifecycle Status
Active

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly

Datasheet

Datasheet not available yet — request it from our team.