Skip to content
PLC - ControlLogix 5580 Controllersby Allen Bradley

1756-OX8I

ControlLogix 8 Pt Digital Relay Module

N.O./N.C. Isolated Relay Output 8 Pts (36 Pin)

Specifications

Isolation
250 V continuous between outputs
Number Of Channels
8
Bounce time, mean
1.2 µs
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Contact current rating
1A @ 5...30V DC, 0.5A @ 48V DC, 0.22A @ 125V DC, 1.5A @ 120V AC, 50/60 Hz, 0.75A @ 240V AC, 50/60 Hz
Current draw
100mA @ 5.1V, 100mA @ 24V
Digital inputs configurable
0
Digital outputs configurable
0
EFT/B immunity
±4kV @ 5kHz on signal ports
Emissions
IEC 61000-6-4
Enclosure type
None (open-style)
ESD immunity
6 kV contact discharges, 8 kV air discharges
Expected contact life
300 kHz, resistive, 100 kHz, inductive
Fusing
Not protected. A fused IFM is recommended to help protect outputs
Initial contact resistance, max
100 mΩ @ 6V @ 1A
Isolation voltage
250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output
Load current per point, min
10 mA
Module keying
Electronic, software configurable
Nonoperating temperature
-40 °C
North American temperature code
T4A
Off-state leakage current per point, max
0 mA
Operating temperature
0 to 60 °C
Operating voltage
5...125V DC @ 10...240V AC
Oscillatory surge withstand
IEEE C37.90.1: 3kV
Output delay time
OFF to ON: 13 ms maximum, ON to OFF: 13 ms maximum
Outputs
8 N.O., 8 N.C. individually isolated (two points per group)
Pilot duty
C300, R150
Power dissipation, max
3.1 W @ 60 °C (140 °F)
Radiated RF immunity
10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Redundancy
0
Relative humidity
5...95% noncondensing
RTB keying
User-defined mechanical
Scheduled outputs
Synchronization within 16.7 s max, reference to the coordinated system time
Shock
Operating: 30 G, Non operating: 50 G
Short-circuit protection, outputs available
0
Slot width
1
States in fault mode per point
Hold last state, On or Off (Off is default)
States in program mode per point
Hold last state, On or Off (Off is default)
Suitable for safety functions
0
Surge transient immunity
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Surrounding air temperature, max
60 °C
Switching frequency, max
1 ops/3 s (0.3 Hz at rated load)
Thermal dissipation
10.57 btu/h
Total backplane power
2.9 W
Type of digital output
Relay
Type of electric connection
Screw connection
Type of voltage (input voltage)
DC
Vibration
2 G @ 10...500 Hz
Voltage type of supply voltage
DC
Wire category
Wire category: 1
Bulletin
1756
Series
A
Lifecycle Status
Active

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly

Datasheet

Datasheet not available yet — request it from our team.