PLC - ControlLogix 5580 Controllersby Allen Bradley
1756-OW16I
ControlLogix 16 Pt Digital Relay Module
N.O. Isolated Relay Output 16 Pts (36 Pin)
Specifications
- Isolation
- 250 V continuous between outputs
- Bounce time, mean
- 1.2 µs
- Conducted RF immunity
- 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
- Current draw
- 150mA @ 5.1V, 150mA @ 24V
- Digital inputs configurable
- 0
- Digital outputs configurable
- 0
- EFT/B immunity
- ±4kV @ 5kHz on signal ports
- Emissions
- IEC 61000-6-4
- Enclosure type
- None (open-style)
- ESD immunity
- 6 kV contact discharges, 8 kV air discharges
- Expected contact life
- 300 kHz, resistive, 100 kHz, inductive
- Fusing
- Not protected. A fused IFM can be used to help protect outputs. See publication 1492-TD008. However, the ControlLogix, system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and, 1756-TBS6H. Any applic
- Initial contact resistance, max
- 100 mΩ @ 6V @ 1A
- Isolation voltage
- 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output
- Load current per point, min
- 10 mA
- Module keying
- Electronic, software configurable
- Nonoperating temperature
- -40 °C
- North American temperature code
- T4A
- Off-state leakage current per point, max
- 1.5 mA
- Operating temperature
- 0 to 60 °C
- Operating voltage
- 5...125V DC @ 10...240V AC
- Oscillatory surge withstand
- IEEE C37.90.1: 3kV
- Output delay time
- OFF to ON: 10 ms maximum, ON to OFF: 10 ms maximum
- Outputs
- 16 N.O. individually isolated
- Output voltage
- 1A @ 5...30V DC 0.5A @ 48V DC 0.22A @ 125V DC 1.5A @ 120V AC, 50/60 Hz 0.75A @ 240V AC, 50/60 Hz
- Pilot duty
- C300, R150
- Power dissipation, max
- 4.5 W @ 60 °C (140 °F)
- Radiated RF immunity
- 10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
- Redundancy
- 0
- Relative humidity
- 5...95% noncondensing
- RTB keying
- User-defined mechanical
- Scheduled outputs
- Synchronization within 16.7 s max, reference to the coordinated system time
- Shock
- Operating: 30 G, Non operating: 50 G
- Short-circuit protection, outputs available
- 0
- Slot width
- 1
- States in fault mode per point
- Hold last state, On or Off (Off is default)
- States in program mode per point
- Hold last state, On or Off (Off is default)
- Suitable for safety functions
- 0
- Surge transient immunity
- ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
- Surrounding air temperature, max
- 60 °C
- Switching frequency, max
- 1 ops/3 s (0.3 Hz at rated load)
- Thermal dissipation
- 15.35 btu/h
- Total backplane power
- 4.4 W
- Type of digital output
- Relay
- Type of electric connection
- Screw connection
- Type of voltage (input voltage)
- DC
- Vibration
- 2 G @ 10...500 Hz
- Voltage type of supply voltage
- DC
- Wire category
- Wire category: 1
- Bulletin
- 1756
- Series
- A
- Lifecycle Status
- Active
Request a Quote
Need pricing, availability or more details? We'll get back to you.
Datasheet
Datasheet not available yet — request it from our team.