Skip to content
PLC - ControlLogix 5580 Controllersby Allen Bradley

1756-OF8IH

ControlLogix 8 Pt A/O HART Isolated

Isolated Analog Output Module - 8-Channel HART

Specifications

Display
Module Health, In Calibration,Mode
Isolation
250V (continuous), Reinforced,insulation type, outputs to,backplane. Basic insulation,type, output to output, and,outputs to ground.
Number Of Channels
8
Output Signal
4-20mA
Special Features
Supports HART Protocol
Analogue inputs configurable
1
Analogue outputs configurable
0
Calibrated accuracy
0.15% @ 4...20mA, 25 °C (77 °F)
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Current draw
400 mA (estimated) @ 24V @ 24V
Data format
IEEE 32-bit floating point
Drive capability
50...750 Ω with short circuit survival
EFT/B immunity
±2kV @ 5kHz on signal ports
Emissions
IEC 61000-6-4
Enclosure type rating
None (open-style)
ESD immunity
6 kV contact discharges, 8 kV air discharges
Gain drift with temperature
±4 ppm of full scale range/°C
Input, current
1
Input, resistance thermometer
0
Input, resistor
0
Input signal, configurable
1
Input, thermocouple
0
Input, voltage
1
Isolation voltage
250V (continuous), Reinforced insulation type, outputs to backplane, Basic insulation type, output to output, and outputs to ground.
Load reactance
10 µH maximum
Module error
0.3% @ 4...20mA
Module keying
Electronic, software configurable
Module scan time
Estimate 1 s if all channels are HART enabled, Pass through messages, handheld communications, sary masters, communication errors, or configuration changes can significantly increase the update time.
Nonoperating temperature
-40 °C
North American temperature code
T4A
Offset drift
±3 ppm of full scale range/°C (72 nA/°C typical)
Open circuit detection
Current output only (output must be set >=0.1 mA)
Operating temperature
0 °C <Ta <60 °C (32 °F <Ta <140 °F)
Output conversion method
R-Ladder DAC
Output, current
0
Output range
0...20mA @ 4...20mA
Outputs
8 current
Output short circuit protection
Current electronically limited to <=21 mA with no damage
Output signal configurable
0
Output, voltage
0
Overvoltage protection
±24V DC
Power dissipation
6.5 W nominal (maximum), (<6.4 W with 50 Ω load on all channels), (<6.5 W with 250 Ω load on all channels), (<6.7 W with 750 Ω load on all channels)
Radiated RF immunity
10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Relative humidity
5...95% noncondensing
Resolution
15 bit across 24 mA, 732 nA per bit
RTB keying
User-defined mechanical
Settling time
HART not enabled: <23 ms to 95% with resistive loads, HART enabled: <100 ms to 95% with resistive loads
Shock
Operating: 30 G, Non operating: 50 G
Slot width
1
Suitable for safety functions
0
Surge transient immunity
±2kV line-earth (CM) on shielded ports
Surrounding air temperature, max
60 °C
Terminal block torque specifications
1756-TBCH: 0.5 Nm (4.4 in-lb)
Type of electric connection
Screw-/spring clA connection
Vibration
2 G @ 10...500 Hz
Voltage and current ratings
Backplane: 220mA @ 5.1V DC, 360mA @ 24V DC, Output voltage range: 5...30V DC, Output current range: 0...20mA @ 4...20mA
Wire category
2 - on signal ports
Wire size
Single wire connection (1756-TBCH): 0.33...2.1 mm² (22...14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation maximum, Single wire connection (1756-TBS6H): 0.33...2.1 mm² (22...14 AWG) solid or
Wire type
Copper
Bulletin
1756
Series
A
Lifecycle Status
Active

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly

Datasheet

Datasheet not available yet — request it from our team.