PLC - ControlLogix 5580 Controllersby Allen Bradley
1756-OF8IH
ControlLogix 8 Pt A/O HART Isolated
Isolated Analog Output Module - 8-Channel HART
Specifications
- Display
- Module Health, In Calibration,Mode
- Isolation
- 250V (continuous), Reinforced,insulation type, outputs to,backplane. Basic insulation,type, output to output, and,outputs to ground.
- Number Of Channels
- 8
- Output Signal
- 4-20mA
- Special Features
- Supports HART Protocol
- Analogue inputs configurable
- 1
- Analogue outputs configurable
- 0
- Calibrated accuracy
- 0.15% @ 4...20mA, 25 °C (77 °F)
- Conducted RF immunity
- 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
- Current draw
- 400 mA (estimated) @ 24V @ 24V
- Data format
- IEEE 32-bit floating point
- Drive capability
- 50...750 Ω with short circuit survival
- EFT/B immunity
- ±2kV @ 5kHz on signal ports
- Emissions
- IEC 61000-6-4
- Enclosure type rating
- None (open-style)
- ESD immunity
- 6 kV contact discharges, 8 kV air discharges
- Gain drift with temperature
- ±4 ppm of full scale range/°C
- Input, current
- 1
- Input, resistance thermometer
- 0
- Input, resistor
- 0
- Input signal, configurable
- 1
- Input, thermocouple
- 0
- Input, voltage
- 1
- Isolation voltage
- 250V (continuous), Reinforced insulation type, outputs to backplane, Basic insulation type, output to output, and outputs to ground.
- Load reactance
- 10 µH maximum
- Module error
- 0.3% @ 4...20mA
- Module keying
- Electronic, software configurable
- Module scan time
- Estimate 1 s if all channels are HART enabled, Pass through messages, handheld communications, sary masters, communication errors, or configuration changes can significantly increase the update time.
- Nonoperating temperature
- -40 °C
- North American temperature code
- T4A
- Offset drift
- ±3 ppm of full scale range/°C (72 nA/°C typical)
- Open circuit detection
- Current output only (output must be set >=0.1 mA)
- Operating temperature
- 0 °C <Ta <60 °C (32 °F <Ta <140 °F)
- Output conversion method
- R-Ladder DAC
- Output, current
- 0
- Output range
- 0...20mA @ 4...20mA
- Outputs
- 8 current
- Output short circuit protection
- Current electronically limited to <=21 mA with no damage
- Output signal configurable
- 0
- Output, voltage
- 0
- Overvoltage protection
- ±24V DC
- Power dissipation
- 6.5 W nominal (maximum), (<6.4 W with 50 Ω load on all channels), (<6.5 W with 250 Ω load on all channels), (<6.7 W with 750 Ω load on all channels)
- Radiated RF immunity
- 10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
- Relative humidity
- 5...95% noncondensing
- Resolution
- 15 bit across 24 mA, 732 nA per bit
- RTB keying
- User-defined mechanical
- Settling time
- HART not enabled: <23 ms to 95% with resistive loads, HART enabled: <100 ms to 95% with resistive loads
- Shock
- Operating: 30 G, Non operating: 50 G
- Slot width
- 1
- Suitable for safety functions
- 0
- Surge transient immunity
- ±2kV line-earth (CM) on shielded ports
- Surrounding air temperature, max
- 60 °C
- Terminal block torque specifications
- 1756-TBCH: 0.5 Nm (4.4 in-lb)
- Type of electric connection
- Screw-/spring clA connection
- Vibration
- 2 G @ 10...500 Hz
- Voltage and current ratings
- Backplane: 220mA @ 5.1V DC, 360mA @ 24V DC, Output voltage range: 5...30V DC, Output current range: 0...20mA @ 4...20mA
- Wire category
- 2 - on signal ports
- Wire size
- Single wire connection (1756-TBCH): 0.33...2.1 mm² (22...14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation maximum, Single wire connection (1756-TBS6H): 0.33...2.1 mm² (22...14 AWG) solid or
- Wire type
- Copper
- Bulletin
- 1756
- Series
- A
- Lifecycle Status
- Active