PLC - ControlLogix 5580 Controllersby Allen Bradley
1756-LSC8XIB8I
ControlLogix 8 Point Counter Input
10-30 VDC Counters at 40 KHz, 8 Counters / 8 Isolated Inputs, Peer to Peer Input (36 Pin)
Specifications
- Features
- 8 Counters / 8 Isolated Inputs, Peer to Peer Input (36 Pin)
- Change of state
- Any transition
- Conducted RF immunity
- 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
- Counting frequency, max
- 40 khz
- Count range
- 0...2,147,483,648 (31-bit counter)
- Current draw
- 275mA @ 5.1V, 3mA @ 24V
- Cyclic update time
- 0.2 ms
- Digital inputs configurable
- 1
- Digital outputs configurable
- 0
- EFT/B immunity
- ±4kV @ 5kHz on signal ports
- Emissions
- IEC 61000-6-4
- Enclosure type
- None (open-style)
- ESD immunity
- 6 kV contact discharges, 8 kV air discharges
- Input delay time
- OFF to ON: 14 µs nom/23 µs max + user-configurable filter time of 0...30,000 µs, ON to OFF: 14 µs nom/23 µs max + user-configurable filter time of 0...30,000 µs
- Input impedance, max
- 6 kΩ @ 30V DC
- Inputs
- 8 individually isolated, standard input or counter-control functionality
- Input voltage, nom
- 24V DC
- Isolation voltage
- 250V (continuous), reinforced insulation type, inputs to backplane, 250V (continuous), basic insulation type, input to input
- Module keying
- Electronic, software configurable
- Nonoperating temperature
- -40 °C
- North American temperature code
- T4A
- Number of counters
- 8 individually isolated
- Off-state current, max
- 1.5 mA
- Off-state voltage, max
- 5V
- ON-state current, max
- 5mA @ 30V DC
- On-state current, min
- 2mA @ 10V DC
- Operating temperature
- 0 to 60 °C
- Operating voltage
- 10...30V DC
- Power dissipation
- 3.8 W @ 60 °C (140 °F)
- Radiated RF immunity
- 10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
- Redundancy
- 0
- Relative humidity
- 5...95% noncondensing
- Reverse polarity protection
- Reverse polarity protection: Yes
- RTB keying
- User-defined mechanical
- Shock
- Operating: 30 G, Non operating: 50 G
- Short-circuit protection, outputs available
- 0
- Slot width
- 1
- Suitable for safety functions
- 0
- Surge transient immunity
- ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
- Surrounding air temperature, max
- 60 °C
- Thermal dissipation
- 12.97 btu/h
- Total backplane power
- 1.47 W
- Type of electric connection
- Screw connection
- Vibration
- 2 G @ 10...500 Hz
- Voltage category
- 12/24V DC sink/source
- Voltage type of supply voltage
- DC
- Wire category
- 1 - on signal ports
- Bulletin
- 1756
- Series
- A
- Lifecycle Status
- Active
Request a Quote
Need pricing, availability or more details? We'll get back to you.
Datasheet