Skip to content
PLC - ControlLogix 5580 Controllersby Allen Bradley

1756-IF6I

ControlLogix 6 Point Isolated A/I Module

Isolated Analog Input-Current/Voltage 6 Pts (20Pin)

Discontinued by the manufacturer — contact us for availability, spares or a recommended replacement.

Specifications

Display
Module Health, In Calibration,Mode
Input Signal
+/- 10V, 0-10.5V, 0-5.25V,0-21mA
Isolation
250 V continuous between,inputs
Number Of Channels
6
Special Features
Per Point Isolation
Analogue inputs configurable
1
Analogue outputs configurable
0
Calibrated accuracy
Better than 0.1% of range @ 25 °C (77 °F)
Channel bandwidth
15 Hz
Common mode noise rejection
120 dB @ 60 Hz, 100 dB @ 50 Hz
Conducted RF immunity
10V rms with 1 kHz sine wave 80% AM from 150 kHz...80 MHz on shielded signal ports
Current draw
250mA @ 5.1V, 100mA @ 24V
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
EFT/B immunity
±2kV @ 5kHz on shielded signal ports
Emissions
IEC 61000-6-4
Enclosure type rating
None (open-style)
ESD immunity
6 kV contact discharges, 8 kV air discharges
Gain drift with temperature
Voltage: 35 ppm/°C, 80 ppm/°C maximum, Current: 45 ppm/°C, 90 ppm/°C maximum
Input, current
1
Input impedance
Voltage: >10 MΩ, Current: 249 Ω
Input range
±10.5V @ 0...10.5V, 0...5.25V @ 0...21mA
Input, resistance thermometer
0
Input, resistor
0
Inputs
6 individually isolated
Input signal, configurable
1
Input, thermocouple
0
Input, voltage
1
Isolation voltage
250V (continuous), basic insulation type, input channels-to-backplane, and input channel-to-channel Routine tested at 1350V AC @ 2s
Module conversion method
Sigma-Delta
Module error
0.54% of range
Module input scan time, min
25 ms minimum - floating point, 10 ms minimum - integer
Module keying
Electronic, software configurable
Nonoperating temperature
-40 °C
Normal mode noise rejection
60 dB @ 60 Hz
North American temperature code
T4A
Offset drift
2 µV/°C
Onboard data alarming
1
Open circuit detection time
Positive full scale reading within 5 s
Operating temperature
0 °C
Output, current
0
Output signal configurable
0
Output, voltage
0
Overvoltage protection
Voltage: 120V AC/DC maximum, Current: 8V AC/DC (with onboard current resistor), maximum
Power dissipation
Voltage: 3.7 W, maximum, Current: 4.3 W, maximum
Radiated RF immunity
10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Real-time channel sampling
1
Relative humidity
5...95% noncondensing
Resolution
16 bit, 10.5V: 343 µV/bit, 0...10.5V: 171 µV/bit, 0...5.25V: 86 µV/bit, 0...21 mA: 0.34 µA/bit
RTB keying
User-defined mechanical
Scaling to engineering units
1
Settling time
<80 ms to 5% of full scale
Shock
Operating: 30 G, Nonoperating: 30 G
Slot width
1
Suitable for safety functions
0
Surge transient immunity
±2 kV line-earth (CM) on shielded signal ports
Surrounding air temperature, max
60 °C
Thermal dissipation
Voltage: 12.62 BTU/hr, Current: 14.32 BTU/hr
Total backplane power
3.7 W
Type of electric connection
Screw-/spring clA connection
Vibration
2 G @ 10...500 Hz
Wire category
Category: 2
Bulletin
1756
Series
A
Lifecycle Status
Discontinued

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly

Datasheet