Skip to content
PLC - ControlLogix 5580 Controllersby Allen Bradley

1756-IF4FXOF2F

ControlLogix 4 Point Analog Comb Module

Fast Analog 4 Cur-Volt In/2 Cur-Volt Out 36 Pin)

Specifications

Display
Module Health, In Calibration,Mode
Input Signal
+/- 10V, 0-10.5V, 0-5.25V.,0-21mA
Isolation
None between channels (Single,Ended)
Output Signal
+/- 10.4V, 0-21mA
Special Features
Sub-ms channel scans,Synchronized sAling across,multiple modules
Analogue inputs configurable
1
Analogue outputs configurable
0
Calibrated accuracy
Input: 0.05% of range immediately after calibration Better than 0.1% of range within calibration interval @ 25 °C (77 °F), Output: 0.05% of range immediately after calibration Better than 0.1% of range within calibration interval @ 25 °C (77 °F)
Conducted RF immunity
10V rms with 1 kHz sine wave 80% AM from 150 kHz...80 MHz on shielded signal ports
Current draw
375mA @ 5.1V, 100mA @ 24V
Data format
Integer mode (left justified, 2 s complement) IEEE 32-bit floating point
Drive capability
Voltage: >2000 Ω, Current: 0...750 Ω
EFT/B immunity
±2kV @ 5kHz on shielded signal ports
Emissions
IEC 61000-6-4
Enclosure type rating
None (open-style)
ESD immunity
6 kV contact discharges, 8 kV air discharges
Gain drift with temperature
Voltage: 25 ppm/°C maximum, input, Current: 35 ppm/°C maximum, input, Voltage: 25 ppm/°C maximum, output, Current: 50 ppm/°C maximum, output
Input conversion method
Successive approximation
Input, current
1
Input impedance
Voltage: >1 MΩ, Current: 249 Ω
Input range
±10V @ 0...10V, 0...5V @ 0...20mA
Input, resistance thermometer
0
Input, resistor
0
Input signal, configurable
1
Input, thermocouple
0
Input, voltage
1
Isolation voltage
250V (continuous), Reinforced insulation type, inputs and outputs to backplane, No isolation between individual inputs or outputs
Module error
Input: 0.2% of range, Voltage: 0.2% of range, output, Current: 0.3% of range, output
Module keying
Electronic, software configurable
Module scan time
300 µs minimum
Nonoperating temperature
-40 °C
North American temperature code
T4A
Number, input
4 high-speed, subms, differential
Number, output
2 high-speed voltage or current
Offset drift
50 µV/°C, 1 µV/°C
Open circuit detection time
Input: Positive full-scale reading within 1 s, Output: Current output only (output must be set to >0.1 mA)
Operating temperature
0 °C <Ta <60 °C (32 °F <Ta <140 °F)
Output conversion method
R-Ladder DAC, monotonicity with no missing codes
Output, current
0
Output range
±10V, 0…20 mA
Output settling time
<2 ms to 95% of final value with resistive loads
Output signal configurable
0
Output, voltage
0
Overvoltage protection
Voltage: 30V DC, input, Current: 8V AC/DC, input, Output: 24V DC
Power consumption
4.3 W
Power dissipation
Voltage: 4.3 W, Current: 4.7 W
Radiated RF immunity
10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2700...6
Relative humidity
5...95% noncondensing
Repeatability
±1 least significant bit (LSB)
Resolution
Input: Approx 14 bit across ±10.5V DC (21V total), ±10.5V range: 1.3 mV/bit, 14 bit effective, 0...10.5V range: 1.3 mV/bit, 13 bit effective, 0...5.25V range: 1.3 mV/bit, 12 bit effective, Approx 12 bit across 21mA @ 0...21mA range: 5.25 µA/bit, Output
RTB keying
User-defined mechanical
Shock
Operating: 30 G, Non operating: 50 G
Short circuit protection
Electronically current limited to 21 mA or less
Slot width
1
Suitable for safety functions
0
Surge transient immunity
±2 kV line-earth (CM) on shielded signal ports
Surrounding air temperature, max
60 °C
Terminal block torque specifications
1756-TBCH: 0.5 Nm (4.4 in-lb)
Thermal dissipation
Voltage: 14.66 BTU/hr, Current: 16.02 BTU/hr
Type of electric connection
Screw-/spring clA connection
Update period for all channels (RPI), min
1 ms
Vibration
2 G @ 10...500 Hz
Voltage and current ratings
Backplane: 375mA @ 5.1V DC, 100mA @ 24V DC, Analog inputs: -10...+10V @ 4...20mA, Analog outputs: -10...+10V @ 4...20mA
Wire category
2 - on signal ports
Wire size
Single wire connection (1756-TBCH): 0.33...2.1 mm² (22...14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation maximum, Single wire connection (1756-TBS6H): 0.33...2.1 mm² (22...14 AWG) solid or
Bulletin
1756
Series
B
Lifecycle Status
Active

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly

Datasheet

Datasheet not available yet — request it from our team.