PLC - ControlLogix 5580 Controllersby Allen Bradley
1756-HSC
ControlLogix High Speed Counter Module
2 Channel / 4 Output High Speed Counter (36 Pin)
Specifications
- Conducted RF immunity
- 10V rms with 1 kHz sine wave 80% AM from 150 kHz...80 MHz on shielded signal ports
- Counter, max
- 1 mhz
- Counting frequency, max
- 1000 khz
- Count range
- 0...16, 777, 214
- Current draw
- 300mA @ 5.1V, 3mA @ 24V
- Current limit
- <4 A
- Debounce filter, max
- 70 Hz
- Digital inputs configurable
- 1
- Digital outputs configurable
- 0
- EFT/B immunity
- ±4kV @ 5kHz on power ports, ±4kV @ 5kHz on signal ports
- Emissions
- IEC 61000-6-4
- Enclosure type
- None (open-style)
- Encoder, max
- 250 khz
- ESD immunity
- 6 kV contact discharges, 8 kV air discharges
- Input current, min
- 4 mA
- Input current, nom
- 15 mA
- Input frequency, max
- 1 MHz in counter modes (A input), 500 kHz in rate measurement mode (A input), 250 kHz in encoder mode (A/B inputs, X1 or X4), 70 Hz with filter enabled
- Inputs per counter
- 3 (A, B, Z for gate/reset)
- Isolation voltage
- 125V (continuous), basic insulation type, input group-to-backplane, 30V (continuous), basic insulation type, input group-to-input group
- Load current per point, min
- 5V ops: 3mA @ 12/24V ops: 40 mA
- Module keying
- Electronic, software configurable
- Nonoperating temperature
- -40 °C
- North American temperature code
- T4
- Number of counters
- 2 counters
- Off-state leakage current per point, max
- 300 µA
- On-state voltage drop, max
- 0.55 V
- Operating temperature
- 0 to 60 °C
- Operating voltage
- 5V ops: 4.5...5.5V DC @ 12/24V ops: 10...26.4V DC
- Output control
- Up to two outputs are assigned to each counter channel, each output can have two ‘turn-on’ and ’turn-off’ preset values
- Output current rating, per point
- 20mA @ 4.5...5.5V DC, 1.0A @ 10...31.2V DC
- Output delay time
- OFF to ON: 20 µs nominal, 50 µs maximum, ON to OFF: 60 µs nominal, 300 µs maximum
- Outputs
- 4 (2 points/group)
- Power dissipation, max
- 5.6 W @ 60 °C(140 °F)
- Radiated RF immunity
- 10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
- Rate measurement, max
- 500 khz
- Relative humidity
- 5...95% noncondensing
- Reverse polarity protection
- Yes (if wired incorrectly, module outputs can be permanently disabled.)
- RTB keying
- User-defined mechanical
- Shock
- Operating: 30 G, Non operating: 50 G
- Short circuit protection
- Electronic (remove overload and toggle On/Off to restore.)
- Short-circuit protection, outputs available
- 0
- Slot width
- 1
- Suitable for safety functions
- 0
- Surge current per point
- 2 A for 10 ms every 1 s @ 60 °C (140 °F)
- Surge transient immunity
- ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports, ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports, ±2 kV line-earth (CM) on shielded ports
- Surrounding air temperature, max
- 60 °C
- Thermal dissipation
- 19.1 btu/h
- Total backplane power
- 1.6 W
- Type of electric connection
- Screw connection
- Vibration
- 2 G @ 10...500 Hz
- Voltage type of supply voltage
- DC
- Wire category
- 2 on signal ports, 1 on power ports
- Bulletin
- 1756
- Series
- D
- Lifecycle Status
- Active
Request a Quote
Need pricing, availability or more details? We'll get back to you.
Datasheet
Datasheet not available yet — request it from our team.