Skip to content
PLC - ControlLogix 5580 Controllersby Allen Bradley

1756-HSC

ControlLogix High Speed Counter Module

2 Channel / 4 Output High Speed Counter (36 Pin)

Specifications

Conducted RF immunity
10V rms with 1 kHz sine wave 80% AM from 150 kHz...80 MHz on shielded signal ports
Counter, max
1 mhz
Counting frequency, max
1000 khz
Count range
0...16, 777, 214
Current draw
300mA @ 5.1V, 3mA @ 24V
Current limit
<4 A
Debounce filter, max
70 Hz
Digital inputs configurable
1
Digital outputs configurable
0
EFT/B immunity
±4kV @ 5kHz on power ports, ±4kV @ 5kHz on signal ports
Emissions
IEC 61000-6-4
Enclosure type
None (open-style)
Encoder, max
250 khz
ESD immunity
6 kV contact discharges, 8 kV air discharges
Input current, min
4 mA
Input current, nom
15 mA
Input frequency, max
1 MHz in counter modes (A input), 500 kHz in rate measurement mode (A input), 250 kHz in encoder mode (A/B inputs, X1 or X4), 70 Hz with filter enabled
Inputs per counter
3 (A, B, Z for gate/reset)
Isolation voltage
125V (continuous), basic insulation type, input group-to-backplane, 30V (continuous), basic insulation type, input group-to-input group
Load current per point, min
5V ops: 3mA @ 12/24V ops: 40 mA
Module keying
Electronic, software configurable
Nonoperating temperature
-40 °C
North American temperature code
T4
Number of counters
2 counters
Off-state leakage current per point, max
300 µA
On-state voltage drop, max
0.55 V
Operating temperature
0 to 60 °C
Operating voltage
5V ops: 4.5...5.5V DC @ 12/24V ops: 10...26.4V DC
Output control
Up to two outputs are assigned to each counter channel, each output can have two ‘turn-on’ and ’turn-off’ preset values
Output current rating, per point
20mA @ 4.5...5.5V DC, 1.0A @ 10...31.2V DC
Output delay time
OFF to ON: 20 µs nominal, 50 µs maximum, ON to OFF: 60 µs nominal, 300 µs maximum
Outputs
4 (2 points/group)
Power dissipation, max
5.6 W @ 60 °C(140 °F)
Radiated RF immunity
10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Rate measurement, max
500 khz
Relative humidity
5...95% noncondensing
Reverse polarity protection
Yes (if wired incorrectly, module outputs can be permanently disabled.)
RTB keying
User-defined mechanical
Shock
Operating: 30 G, Non operating: 50 G
Short circuit protection
Electronic (remove overload and toggle On/Off to restore.)
Short-circuit protection, outputs available
0
Slot width
1
Suitable for safety functions
0
Surge current per point
2 A for 10 ms every 1 s @ 60 °C (140 °F)
Surge transient immunity
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports, ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports, ±2 kV line-earth (CM) on shielded ports
Surrounding air temperature, max
60 °C
Thermal dissipation
19.1 btu/h
Total backplane power
1.6 W
Type of electric connection
Screw connection
Vibration
2 G @ 10...500 Hz
Voltage type of supply voltage
DC
Wire category
2 on signal ports, 1 on power ports
Bulletin
1756
Series
D
Lifecycle Status
Active

Request a Quote

Need pricing, availability or more details? We'll get back to you.

* Required. Please give an email or a phone number.

Prefer WhatsApp? Message us directly

Datasheet

Datasheet not available yet — request it from our team.