PLC - ControlLogix 5580 Controllersby Allen Bradley
1756-CFM
ControlLogix Config Flowmeter Module
2 Channel/2 Out Configurable Flowmeter (20Pin)
Specifications
- Conducted RF immunity
- 10V rms with 1 kHz sine wave 80% AM from 150 kHz...80 MHz on shielded signal ports
- Count range, max
- 2, 147, 483, 647
- Current draw
- 300mA @ 5.1V, 16mA @ 24V
- Digital inputs configurable
- 1
- Digital outputs configurable
- 0
- EFT/B immunity
- ±4kV @ 5kHz on unshielded output and power ports, ±4kV @ 5kHz on shielded input ports
- Emissions
- IEC 61000-6-4
- Enclosure type
- None (open-style)
- ESD immunity
- 6 kV contact discharges, 8 kV air discharges
- Filtering (inputs F0 & F1)
- Firmware selectable: high-speed 100 kHz or low-pass filter for frequencies <70 Hz
- Flowmeter input impedance
- 5 kΩ ±30% resistive
- Flowmeter input voltage
- ±30V, selectable input thresholds of 50mV @ 1.3V and 4V: ±30V peak unterminated open circuit voltage, magnetic pickup, TTL compatible, input voltage >1.3V DC is Logic 1 and -0.7...1.3V DC is Logic 0, 12...24V DC powered preA output, 4V DC threshold
- Frequency
- Resolution: 0.0005 Hz
- Gate input on-state current, min
- 4 mA
- Gate input on-state current, nom
- 15 mA
- Gate input voltage range
- 5V ops: 4.5...5.5V DC @ 12/24V ops: 10...26.4V DC
- High resolution, max
- 100 khz
- Input frequency, max
- 100 kHz @ flowm inputs (overrange occurs at 100 kHz)
- Input sampling period
- User selectable
- Inputs
- Two flowm (F) inputs used for all modes, Two gate inputs used in Totalizer mode for prover/store count, 4 (2 per channel)
- Isolation voltage
- 250V (continuous), reinforced insulation type, I/O-to-backplane, 250V (continuous), basic insulation type, I/O group-to-group
- Mechanical filter debouncing (Z0 & Z1 Inputs)
- Software selectable
- Module keying
- Electronic, software configurable
- Nonoperating temperature
- -40 °C
- North American temperature code
- T4
- Off-state leakage current, max
- <300 µA @ 31.2V DC
- On-state voltage drop, max
- 0.6 Ω x current
- Operating temperature
- 0 to 60 °C
- Output control
- Any number of outputs is assignable to any of two flowm channels each output can have 2 “turn-on” and “turn-off” preset values
- Output current per point
- 1 @ 10...31.2V DC @ 20mA @ 4.5...5.5V DC
- Output reverse polarity protection
- Yes (if wired incorrectly, module outputs can be permanently disabled.)
- Outputs
- 2 current sourcing
- Output short circuit protection
- Electronic (no indication of fault. remove overload and toggle output on/off to restore.)
- Output switching time
- <50 µs turn on, <300 µs turn off, Outputs triggered by Total, all other “turn-on” and “turn-off” times <1 ms
- Output type
- IEC 1 A 24V DC
- Output voltage range, nom
- 5V ops: 4.5...5.5V DC @ 3...20mA load per point, 12/24V ops: 10...31.2V DC @ 40mA...1 A load per point
- Output voltage source
- Customer supplied
- Overload current
- Electronic (<4 A)
- Power dissipation, max
- 6 W @ 60 °C (140 °F)
- Radiated RF immunity
- 10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
- Redundancy
- 0
- Relative humidity
- 5...95% noncondensing
- Reverse polarity protection
- Outputs only
- RTB keying
- User-defined mechanical
- Shock
- Operating: 30 G, Non operating: 50 G
- Short-circuit protection, outputs available
- 0
- Slot width
- 1
- Suitable for safety functions
- 0
- Surge current
- 2 A @ 50 ms, repeatable every 2s
- Surge transient immunity
- ±1 kV line-line (DM) and ±2 kV line-earth (CM) on unshielded output and power ports, ±2 kV line-earth (CM) on shielded input ports
- Surrounding air temperature, max
- 60 °C
- Thermal dissipation
- 20.4 btu/h
- Total backplane power
- 1.7 W
- Totalizer fill and prover
- 1
- Type of electric connection
- Screw connection
- Vibration
- 2 G @ 10...500 Hz
- Voltage type of supply voltage
- DC
- Wire category
- 2 on signal ports, 1 on power ports
- Bulletin
- 1756
- Series
- B
- Lifecycle Status
- Active
Request a Quote
Need pricing, availability or more details? We'll get back to you.
Datasheet
Datasheet not available yet — request it from our team.